Citation
Nor, N.M. and Haddad, A. and Griffiths, H. (2005) Determination of Threshold Electric Field<tex>$rm E _rm C$</tex>of Soil Under High Impulse Currents. IEEE Transactions on Power Delivery, 20 (3). pp. 2108-2113. ISSN 0885-8977
PDF
1527.pdf Download (0B) |
Official URL: http://dx.doi.org/10.1109/TPWRD.2005.848761
Abstract
A threshold electric-field intensity (E-c), above which soil ionization occurs, has been known to be important to predict soil behavior under high impulse currents. However, published results [1]-[5] reveal a wide range of values of E-c (1.3 to 20 kV/cm) and the effects of many other factors such as soil resistivity, impulse polarity, and electrode geometry require further investigation. The aim of this investigation was to quantify the effects of soil resistivity, the impulse polarity on the threshold electric field (E-c) of soil under fast transients.
Item Type: | Article |
---|---|
Subjects: | T Technology > TA Engineering (General). Civil engineering (General) |
Divisions: | Faculty of Engineering (FOE) |
Depositing User: | Ms Rosnani Abd Wahab |
Date Deposited: | 12 Aug 2011 01:17 |
Last Modified: | 12 Aug 2011 01:17 |
URII: | http://shdl.mmu.edu.my/id/eprint/2215 |
Downloads
Downloads per month over past year
Edit (login required) |