Citation
Basu, Kartik Prasad and George, Moleykutty (2014) Maintaining balanced three-phase load voltage during single-phase auto-reclosing in medium voltage distribution lines. IET Generation, Transmission and Distribution, 8 (5). pp. 798-802. ISSN 1751-8687
Text
Maintaining balanced three-phase load voltage during single-phase auto-reclosing in medium voltage distribution lines.pdf Restricted to Repository staff only Download (246kB) |
Abstract
Single-phase auto-reclosing (SPAR) is used for restoring power supply to clear temporary single-phase to ground fault in medium-voltage distribution systems. A zigzag winding grounding transformer connected at the remotest load bus rebuilds the three-phase voltage during the SPAR dead time. A distribution system having more than one branch needs one zigzag transformer at the remotest end of each branch. Build-up three-phase voltage during SPAR is not balanced. Operation of distributed generator connected to the system during SPAR needs the voltage to be balanced. Magnitude of the negative sequence voltage may be reduced by connecting capacitor in series with the neutrals of each zigzag transformer.
Item Type: | Article |
---|---|
Subjects: | T Technology > T Technology (General) |
Divisions: | Faculty of Engineering (FOE) Faculty of Engineering and Technology (FET) |
Depositing User: | Ms Suzilawati Abu Samah |
Date Deposited: | 03 Jul 2014 00:56 |
Last Modified: | 25 Jul 2014 03:27 |
URII: | http://shdl.mmu.edu.my/id/eprint/5543 |
Downloads
Downloads per month over past year
Edit (login required) |