Abstract

In this paper, experimental test set and test results on the performance of practical earthing systems under high impulse currents are presented where the earthing systems consist of 3 earthing systems configurations, 2, 3 and 4 rod electrodes. Calibration tests using linear test load in order to validate the transducers adopted for this study are also discussed in this paper. This paper also presents the selection of the remote earth and some data from previously published work of the same site and earthing systems configurations under low magnitude currents and at power frequency. Soil ionisation characteristics on the real earthing systems were investigated. The performance of earthing systems are investigated based on its voltage and current shapes, earth pre- and post-ionisation resistance values and time delays. It was found that under impulse conditions, earthing systems behave differently where the earth resistance was found to be non-linear which are due to thermal and ionisation processes

Item Type: Article
Subjects: Q Science > QC Physics
Divisions: Faculty of Engineering (FOE)
Depositing User: Users 1102 not found.
Date Deposited: 28 Dec 2012 04:17
Last Modified: 28 Dec 2012 04:17
URI: http://shdl.mmu.edu.my/id/eprint/3742

Actions (login required)